|
CSFCA/FMAC Response to IAFC's Proposed
Changes to NFPA 72
On Friday, January 14, 2011, those of you
that are members of the International
Association of Fire Chiefs (IAFC) received
an “IAFC
Call to Action” Regarding NFPA 72
and Commercial False Alarms by email (see
below). The “Call to Action” brought to
member attention that IAFC has submitted a
series of proposals
via the NFPA code change process to update
NFPA 72, National Fire Alarm and Signaling
Code, with the stated intent to provide
solutions to the problems caused by the
number of false alarms in commercial
facilities. The “Call to Action” provided a
link to a
fact sheet
that outlines the IAFC proposal to NFPA 72.
Also this past Friday, the CSFCA Board of
Directors heard a presentation by David
Lowrey in his capacity as President of the
Fire Marshal Association of Colorado (FMAC)
on FMAC’s opposition to the IAFC’s proposed
changes to NFPA 72. FMAC requested that the
CSFCA support their position on the proposed
changes.
Specifically, on the IAFC proposal to allow
up to 90 seconds for the supervising station
to verify an alarm before notifying the fire
department, it was argued that this proposal
was not fixing the problem of reducing the
number of unwanted or nuisance alarms.
Further, by delaying the response, you can
actually be increasing the risk to fire
fighters and the occupants of the building
in a fire situation. Eliminating emergency
response to fire alarms will only allow the
owner of the system to ignore a
dysfunctional fire alarm system. Occupants
of the building will become more complacent
in not evacuating and in an actual fire
situation; emergency response personal will
be delayed responding to the building
allowing the fire to possible double in
size.
On the IAFC proposal concerning point ID
communication, it was argued that:
·
many buildings simply don’t need an
addressable type fire alarm system to meet
the requirements of the governing code for
that area;
·
any jurisdiction has the legal right to
amend their adopted code to require point ID
if that’s their preference;
·
the requirement for point ID for all
buildings will certainly increase the cost
of the fire alarm systems; and
·
there is no technical justification for
increasing the cost of fire alarm systems
for a building that is required to only
monitor a sprinkler system, elevator recall
or duct detectors.
Note: Please see the
letter from CSFCA and
FMAC to NFPA’s Supervising Station Fire
Alarm Systems Technical Committee
for a full discussion of the basis for
opposition to the proposed changes.
Following discussion, the CSFCA Board of
Directors voted unanimously to sign a
joint letter with FMAC
to NFPA’s Supervising Station Fire Alarm
Systems Technical Committee in
opposition to the IAFC proposals. The CSFCA
and FMAC believe that unwanted and nuisance
alarms can be reduced significantly through
proper design, installation, acceptance
commissioning, and on-going inspection,
testing and maintenance as outlined in NFPA
72.
This action is in advance of the NFPA 72
Technical Committee meetings later this
week.
Questions or comments concerning this action
may be directed to the
CSFCA Executive
Director.
Posted 01-18-11 |